CDT-2000/5000 series Carbon Dioxide CO2 Transmitters

CDT-2000/5000 series

Our CDT-2000/5000 carbon dioxide transmitter is designed for measuring CO2 in indoor environments.

The CDT-2000/5000 converts the the values measured in the ranges of optionally 0-2000 ppm or 0-5000 ppm into a linear 0-10 V output signal.

The CO2 value is measured via the NDIR sensor, which is able to compensate possible pollution with the help of its 2-ray measuring principle. Optionally, our CDT-2000/5000 is available with an additional sensor for measuring temperature and humidity.

 

Model
Product code
Output ppm
Output Temp.
Output Humidity
CDT-2000/5000-V 30.01.001 0-10V
CDT-2000/5000-T-V 30.01.002 0-10V 0-10V
CDT-2000/5000-T-H-V 30.01.003 0-10V 0-10V 0-10V
CDT-2000/5000-A 30.02.001 4-20mA
CDT-2000/5000-T-A 30.02.002 4-20mA 4-20mA
CDT-2000/5000-H-A 30.02.003 4-20mA 4-20mA
Power supply: At 0 … 10 V: 16 … 24 VDC or 24 VAC
At 4 … 20 mA: 16 … 24 VDC
Power consumption: 9 mA
Electrical connection: Screw clamps
Output: 0…10 V or 4-20mA
Sensorelement: NDIR – Sensor mit Autokalibration durch Dual – Beam Verfahren
Measuring range CO2: 0…2000 ppm / 0…5000 ppm
Accuracy: < ± (50ppm +2% of scale reading) at 25°C and 1013 mbar
Optional:
Temperature: 0…10 V or 4-20mA / 0°C…+50°C
Accuracy: ±0,5°C
Humidity: 0…10 V or 4-20mA / 0…100% r.h.
Accuracy: < ± 3% at 25°C between 10…90% r.h.
Operating temperature: 0°C…+50°C
Humidity: 10…95% r.h.
Protection class: IP20
Casing: Material ABS
Colour: RAL9010