AQT-2000-Duct series Air Quality (VOC) Transmitters for Duct
AQT-2000-Duct series
Our AQT-2000-Duct series are designed for measuring the air quality in ducts of ventilation systems, optionally with 0-10 V or 4-20 mA output.
The AQT-2000-Duct has a VOC/mixed gas sensor. The CO2 equivalents are derived from a conforming algorithm as the odor emissions are overlaying the CO2 value (see graphics below). Long-term drifting and operational deterioration can be eliminated by regularly running the automatic calibration.
Long-term drifting and operational deterioration can be eliminated by regularly running the automatic calibration.
Item Code | Output ppm | Output Temp. | Output Humiditiy |
AQT-2000-Duct-V | 0-10V | ||
AQT-2000-Duct-T-V | 0-10V | 0-10V | |
AQT-2000-Duct-T-H-V | 0-10V | 0-10V | 0-10V |
AQT-2000-Duct-A | 4-20mA | ||
AQT-2000-Duct-T-A | 4-20mA | 4-20mA | |
AQT-2000-Duct-H-A | 4-20mA | 4-20mA |
Power supply: | At 0 … 10 V: 16 … 24 VDC or 24 VAC at 4…20mA: 15…36V/DC |
Power consumption: | max. 45 mA |
Output: | 0…10V or 4…20mA |
Measuring range: | 0-2000ppm |
Calibration: | Good air ca. 1 V … 4 mA = 250 ppm CO2 equivalent 5 V … 12 mA = 1175 ppm CO2 equivalent 10 V … 20 mA = 2000 ppm CO2 equivalent |
Operating temperature: | 0…+50°C |
Humidity: | 5…95% r.h. |
Protection class: | IP65 (Housing) |
Casing: | ABS |
Mounting equipment (included): | Mounting flange |