CDT-2000/5000-Duct Carbon Dioxide CO2 Transmitters for Duct
Our CDT-2000/5000-Duct is designed for measuring CO2 in air ducts of ventilation systems.
The CDT-2000/5000-Duct converts the the values measured in the ranges of optionally 0-2000 ppm or 0-5000 ppm into output signal.
The CO2 value is measured via the NDIR sensor, which is able to compensate possible pollution with the help of its 2-ray measuring principle. Optionally, our CDT-2000/5000-duct is available with an additional sensor for measuring temperature and humidity.
Models
Product Code | Output ppm | Output Temp. | Output Humidity |
CDT-2000/5000-Duct-V | 0-10V | ||
CDT-2000/5000-Duct-T-V | 0-10V | 0-10V | |
CDT-2000/5000-Duct-T-H-V | 0-10V | 0-10V | 0-10V |
CDT-2000/5000-Duct-A | 4-20mA | ||
CDT-2000/5000-Duct-T-A | 4-20mA | 4-20mA | |
CDT-2000/5000-Duct-H-A | 4-20mA | 4-20mA |
Power supply: | At 0 … 10 V: 16 … 24 VDC or 24 VAC At 4 … 20 mA: 16 … 24 VDC |
Power consumption: | < 9 mA |
Electrical connection: | Screw clamps |
Output: | 0…10 V or 4-20mA |
Sensor element: | (NDIR) sensor with automatic backgroand calibration |
Measuring range CO2: | 0…2000 ppm |
Accuracy: | < ± (50ppm 2% of scale reading) at 25°C and 1013 mbar |
Optional: | |
Temperature: | 0 … 10 V or 4-20 mA / -30 °C … +70 °C |
Accuracy: | ± 0,5°C |
Humidity: | 0…10 V or 4-20mA / 0…100% r.h. |
Accuracy: | < 3% at 25°C between 10…90% r.h. |
Operating temperatur: | -20°C…+50°C |
Humidity: | 10…95% r.h. |
Protection class: | IP65 (Housing) |
Casing: | Plastic |
Mounting equipment (included): | Mounting flange |