DPG/PS Combination of pressure gauge and pressure switch
The filter alerts are a solution for systems requiring visual indication of pressure on site, together with switching point signal. The filter alerts are ideal for general-purpose work in air-conditioning and ventilation, especially in monitoring of air filters for contamination.
The available combinations include pressure gauge and pressure switch combination (DPG/PS), and inclined tube manometer and pressure switch combination (MM/PS).
Filter alert: differential pressure gauge – differential pressure switch combination | ||
Product | Measurement range (Pa) | Product code |
DPG200PS200 | 0…200 | 109.001.001 |
DPG500/PS500 | 0…500 | 109.004.001 |
DPG600PS600 | 0…600 | 109.002.001 |
DPG1,5KPS1500 | 0…1500 | 109.003.001 |
Accuracy of gauge (FS 20 °C): | ±2 % |
Switching difference: | DPG200/PS200: 20 Pa DPG300/PS300: 20 Pa DPG500/PS500: 20 Pa DPG600/PS600: 30 Pa DPG1,5K/PS1500: 80Pa |
Accuracy of switching point (Low limit typ.): | DPG200/PS200: 20 Pa ±5 Pa DPG300/PS300: 30 Pa ±5 Pa DPG500/PS500: 30 Pa ±5 Pa DPG600/PS600: 40 Pa ±5 Pa DPG1,5K/PS1500: 100 Pa ±10 Pa |
Accuracy of switching point (High limit typ.): | DPG200/PS200: 200 Pa ±20 Pa DPG300/PS300: 300 Pa ±30 Pa DPG500/PS500: 500 Pa ±30 Pa DPG600/PS600: 600 Pa ±30 Pa DPG1,5K/PS1500: 1500 Pa ±50 Pa |
Electrical rating, resistive load: | 3 A / 250 VAC (DPG200/PS200: 0.1 A / 250 VAC) |
Electrical rating, inductive load: | 2 A / 250 VAC (DPG200/PS200: -) |
Maximum pressure: | 50 kPa |
Service life: | > 1 000 000 switching operations |
Measuring units: | Pa |
Environment: | Operating temperature: -5…+60 °C Storage temperature: -40…+85 °C |
Protection standard: | IP54 |