tSENSE-VAV CO2 , Temperature and Humidity Controller

tSENSE-VAV

 

  • MAINTENANCE-FREE
  • THREE SENSORS IN ONE HOUSING
  • COLOUR TOUCH DISPLAY WITH POSSIBILITY OF CUSTOMIZABLE GUI
  • FLEXIBILITY – TEMPERATURE AND/OR HUMIDITY OPTIONAL
  • IMPROVED HOUSING DESIGN FOR EFFECTIVE MEASUREMENT
  • FIVE YEARS WARRANTY

 

tSENSE VAV is an advanced and versatile three-in-one controller designed for installation in the air-conditioned zone. The unit measures CO2 concentration, temperature and humidity in the ambient air accurately without need for additional compensation ─ true read.

tSENSE VAV combines all the necessary elements for effective climate control in commercial office buildings, hospitals, hotels, schools and other facilities. Using CO2-monitoring for demand control ventilation (DCV) allows healthy, comfortable and cost-effective environment for the occupants. It is flexible in design with temperature control in combination with humidity control. Though suitable for use in many different energy-efficient ventilation strategies, we welcome any discussions for specific needs.

Complies with ASHRAE standard 189.1 (±50ppm @ 1000ppm of measured CO2 value)

070-8-0003 tSENSE VAV Disp T RH RL MB BAC Colour touch display
070-8-0007 tSENSE VAV No Disp No display
Operating Principle Non-dispersive infrared (NDIR)
Measured gas Carbon dioxide (CO2)
Measurement range 0 – 2000ppm
OUT1: 0 – 10VDC
             CO2 600 – 900ppm
             Temperature 22 – 23°C
             Relative Humidity 75 – 85%RH
OUT2:  CO2 0 – 10VDC, 0 – 2000ppm
OUT3:  Temperature 0 – 10VDC, 0 – 50°C
Relay:   CO2 0 – 10VDC, 900 – 1000ppm
Accuracy (CO2) ±30ppm ±3% of reading
Dimensions 125mm x 85mm x 22mm
Dimensions display 49mm x 37mm
Life expectancy >15 years
Operation temperature range 0 – 50°C
Power supply 12VDC, 24VAC/DC
Communication Modbus (MB) or BACnet (BAC) protocol over RS485